OKPH

Specifications
  • Plug-in relay for monitoring the directional sequence of 3-phase voltages
  • 1 N.O. contact
  • Fixed hysteresis cycle
  • Industrial frequency AC operation
  • Solid and rugged construction
  • Excellent shock and vibration resistance
  • Wide range of sockets
  • Retaining clip for secure locking of relay on socket
  • Positive mechanical keying for relay and socket
Description

Relays of the OKPh series are supervision devices for monitoring the directional sequence of phases or detecting the loss of one or more voltages in three phase systems. These components are typically used for detecting faults affecting either a power supply or the sequences of individual phases. The supervision relay can identify undervoltages on one of the 3 phases below a fixed threshold, or detect a phase break: this advantageously prevents the risk of three phase motors operating in single phase mode. In addition, monitoring of the correct R-S-T sequence enables permanent supervision of the status of power supplies to three-phase users, and the avoidance of dangerous incorrect connections. These relays are connected directly to the 400Vac three-phase power line. When the system under supervision is operating correctly, the relay contact remains closed.

The OKPh relay detects the direction of rotation using high quality passive electronic components (R and C) which, in combination with the superior reliability of the electromechanical section, allow these relays to perform key roles in the systems in which they are installed.

The ultra-high reliability and long electrical life expectancy of these components allow them to be used in particularly demanding environments such as, for example, electricity generating stations, electrical transformer stations, and industries using continuous production processes.

Compliance with standards
  • EN 61810-1, EN 61810-2, EN 61810-7 Electromechanical elementary relays
  • EN 60695-2-10 Fire hazard testing
  • EN 50082-2 Electromagnetic compatibility
  • EN 60529 Degrees of protection provided by enclosures
  • EN 60077 Electric equipment for rolling stock - General service conditions and general rules
  • EN 50155 Electronic equipment used on rolling stock
  • EN 61373 Shock and vibration tests, Category 1, Class B
  • EN 45545-2 Requirements for fire behaviour of materials and components – Product No. EL10 – Requirement R26, V0
  • ASTM E162, E662 Standard Test Method for Surface Flammability of Materials, Standard Test Method for Specific Optical Density of Smoke

Download technical drawings 2D/3D

LOGIN / REGISTRATION
PAIR160
  • Connection: Front
  • Terminal type: Spring clamp
  • Mounting: Panel /DIN Rail
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -50…+70°C

Details
48BIP20-I DIN
  • Connection: Front
  • Terminal type: Screw
  • Mounting: Panel /DIN Rail
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

Details
48BL
  • Connection: Front
  • Terminal type: Screw
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

Details
PRIR160
  • Connection: Rear
  • Terminal type: Spring clamp
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -50…+70°C

Details
43IL
  • Connection: Rear
  • Terminal type: Screw
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

 

OBSOLET PRODUCT

 

Details
ADF2
  • Connection: Rear
  • Terminal type: Double faston
  • Mounting: Panel
  • Wire max (mm2): 2 x 2.5
  • Operating temperature: -25…+70°C

Details
65
  • Connection: Rear
  • Terminal type: PCB pins
  • Mounting: PCB
  • Wire max (mm2): -
  • Operating temperature: -25…+70°C

Details